| PEELLE
Door Status LED's (located on the Peelle door board)
- 24V ON = the 24Vdc power to the Peelle board
is good
- ZNS (zone switch) ON = the elevator is at a
floor with a zone interlock contact made
- DOL (door open limit) ON = the hoistway door
is on the open limit switch
- DCL (door close limit) ON = the hoistway door
is on the close limit switch
- GOL (gate oppen limit) ON = the car gate is
on the open limit switch
- GCL (gate close limit) ON = the car gate is
on the close limit switch
- GOFL (gate open final limit) ON = the car gate
is on the final limit switch
- DOFL (door open final limit) ON = the hoistway
door is on the final limit switch
- HTB (heart beat) = flashing green indicates
the board is communicating with the main CPU
|
PEELLE "Field Programmable"
Door Parameters & Timers |
| |
AUTO CLOSE
CLOSE TYPE
OPEN FINALS
SAFETY EDGE
AUTO CLS TMR
PHOTOEYE DIS
FINAL OPEN
GATE TIMEOUT |
=
=
=
=
=
=
=
=
=
=
= |
Y (yes) N (no)
MP (momentary pressure) CP (constant
pressure) BOTH (car gate and hoistway doors final
limits are provided by PEELLE) GATE (final limits
on are on the gate only) NO (no final limits
are provided) Y (yes) N
(no)
_ _ (wait time before the doors auto close)
_ _ (wait time before the doors auto close)
_ _ (the delay to turn off the door open after the doors have reached
the slowdown when
no hoistway final limits are provided)
_ _ (the delay to turn off the gate close after teh gate reached the
slowdown) |